  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en",
    "notes": [
      {
        "category": "summary",
        "text": "Siemens Reyrolle 7SR5 Before V2.70 is affected by multiple vulnerabilities.\n\nSiemens has released a new version for Reyrolle 7SR5 and recommends to update to the latest version.",
        "title": "Summary"
      },
      {
        "category": "general",
        "text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\nhttps://www.siemens.com/gridsecurity",
        "title": "General Recommendations"
      },
      {
        "category": "general",
        "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
        "title": "Additional Resources"
      },
      {
        "category": "legal_disclaimer",
        "text": "The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.",
        "title": "Terms of Use"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "productcert@siemens.com",
      "name": "Siemens ProductCERT",
      "namespace": "https://www.siemens.com"
    },
    "references": [
      {
        "category": "self",
        "summary": "SSA-142885: Multiple Vulnerabilities in Reyrolle 7SR5 Before V2.70 - HTML Version",
        "url": "https://cert-portal.siemens.com/productcert/html/ssa-142885.html"
      },
      {
        "category": "self",
        "summary": "SSA-142885: Multiple Vulnerabilities in Reyrolle 7SR5 Before V2.70 - CSAF Version",
        "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-142885.json"
      }
    ],
    "title": "SSA-142885: Multiple Vulnerabilities in Reyrolle 7SR5 Before V2.70",
    "tracking": {
      "current_release_date": "2026-09-08T00:00:00.000Z",
      "generator": {
        "engine": {
          "name": "Siemens ProductCERT CSAF Generator",
          "version": "1"
        }
      },
      "id": "SSA-142885",
      "initial_release_date": "2026-09-08T00:00:00.000Z",
      "revision_history": [
        {
          "date": "2026-09-08T00:00:00.000Z",
          "legacy_version": "1.0",
          "number": "1",
          "summary": "Publication Date"
        }
      ],
      "status": "interim",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:intdot/<2.70",
                "product": {
                  "name": "Reyrolle 7SR5 < V2.70",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "Reyrolle 7SR5"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2024-42384",
      "cwe": {
        "id": "CWE-190",
        "name": "Integer Overflow or Wraparound"
      },
      "notes": [
        {
          "category": "description",
          "text": "Integer Overflow or Wraparound vulnerability in Cesanta Mongoose Web Server v7.14 allows an attacker to send an unexpected TLS packet and produce a segmentation fault on the application.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2024-42384"
    },
    {
      "cve": "CVE-2024-42385",
      "cwe": {
        "id": "CWE-140",
        "name": "Improper Neutralization of Delimiters"
      },
      "notes": [
        {
          "category": "description",
          "text": "Improper Neutralization of Delimiters vulnerability in Cesanta Mongoose Web Server v7.14 allows to trigger an out-of-bound memory write if the PEM certificate contains unexpected characters.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 4.0,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:L/AC:H/PR:H/UI:R/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2024-42385"
    },
    {
      "cve": "CVE-2024-42386",
      "cwe": {
        "id": "CWE-823",
        "name": "Use of Out-of-range Pointer Offset"
      },
      "notes": [
        {
          "category": "description",
          "text": "Use of Out-of-range Pointer Offset vulnerability in Cesanta Mongoose Web Server v7.14 allows an attacker to send an unexpected TLS packet and produce a segmentation fault on the application.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.2,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2024-42386"
    },
    {
      "cve": "CVE-2024-42391",
      "cwe": {
        "id": "CWE-823",
        "name": "Use of Out-of-range Pointer Offset"
      },
      "notes": [
        {
          "category": "description",
          "text": "Use of Out-of-range Pointer Offset vulnerability in Cesanta Mongoose Web Server v7.14 allows an attacker to send an unexpected TLS packet and force the application to read unintended heap memory space.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 4.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2024-42391"
    },
    {
      "cve": "CVE-2024-42392",
      "cwe": {
        "id": "CWE-140",
        "name": "Improper Neutralization of Delimiters"
      },
      "notes": [
        {
          "category": "description",
          "text": "Improper Neutralization of Delimiters vulnerability in Cesanta Mongoose Web Server v7.14 allows to trigger an infinite loop bug if the input string contains unexpected characters.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 4.0,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:L/AC:H/PR:H/UI:R/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2024-42392"
    },
    {
      "cve": "CVE-2026-62645",
      "cwe": {
        "id": "CWE-306",
        "name": "Missing Authentication for Critical Function"
      },
      "notes": [
        {
          "category": "description",
          "text": "Information is exposed through the web interface that can be used to calculate the current and past session ID numbers. This could allow an attacker to bypass the authentication and gain unauthorized access to the device.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62645"
    },
    {
      "cve": "CVE-2026-62646",
      "cwe": {
        "id": "CWE-331",
        "name": "Insufficient Entropy"
      },
      "notes": [
        {
          "category": "description",
          "text": "A session identifier is generated using an algorithm with insufficient randomness, resulting in a token with low entropy that can be predicted or brute-forced within a feasible number of attempts. This could allow an unauthenticated remote attacker to derive valid session identifiers and bypass authentication.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.4,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62646"
    },
    {
      "cve": "CVE-2026-62647",
      "cwe": {
        "id": "CWE-20",
        "name": "Improper Input Validation"
      },
      "notes": [
        {
          "category": "description",
          "text": "A random number generator is used to generate security-relevant values (such as session identifiers used for authentication purposes) that is not initialized with a True Random Number Generator (TRNG), resulting in a predictable sequence of generated values. This could allow an unauthenticated remote attacker to more easily predict the generated values and impersonate a legitimate authenticated user, potentially gaining unauthorized access to the device.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.4,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62647"
    },
    {
      "cve": "CVE-2026-62648",
      "cwe": {
        "id": "CWE-787",
        "name": "Out-of-bounds Write"
      },
      "notes": [
        {
          "category": "description",
          "text": "The length of the URL component contained in pre-authenticated HTTP messages is not properly validated before appending additional data to it, resulting in an out-of-bounds write condition in memory. This could allow an unauthenticated remote attacker to crash the affected device, causing a reboot and resulting in a denial-of-service condition.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62648"
    },
    {
      "cve": "CVE-2026-62649",
      "cwe": {
        "id": "CWE-770",
        "name": "Allocation of Resources Without Limits or Throttling"
      },
      "notes": [
        {
          "category": "description",
          "text": "The web server does not properly limit or manage system resources when processing a high volume of concurrent HTTP requests. This could allow an unauthenticated remote attacker to cause the entire device to crash and reboot, resulting in a denial-of-service condition.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62649"
    },
    {
      "cve": "CVE-2026-62650",
      "cwe": {
        "id": "CWE-288",
        "name": "Authentication Bypass Using an Alternate Path or Channel"
      },
      "notes": [
        {
          "category": "description",
          "text": "Server-side authorization checks in the web-based management interface are not properly enforced, allowing role-based access control (RBAC) restrictions to be bypassed through manipulation of request data. This could allow an authenticated, low-privileged remote attacker to escalate privileges to an administrative level.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62650"
    },
    {
      "cve": "CVE-2026-62652",
      "cwe": {
        "id": "CWE-215",
        "name": "Insertion of Sensitive Information Into Debugging Code"
      },
      "notes": [
        {
          "category": "description",
          "text": "The device firmware contains binaries from which debugging symbols have not been removed. This could allow an unauthenticated attacker with access to the publicly available firmware update files to more easily reverse engineer the device's firmware, facilitating the identification of further vulnerabilities.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62652"
    },
    {
      "cve": "CVE-2026-62653",
      "cwe": {
        "id": "CWE-787",
        "name": "Out-of-bounds Write"
      },
      "notes": [
        {
          "category": "description",
          "text": "The input received over a proprietary communication protocol that is exposed when the device is placed into a special firmware-update mode is not properly validated, resulting in a memory corruption condition. This could allow an unauthenticated attacker with physical access to the device to cause a crash and potentially execute arbitrary code on the device.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62653"
    },
    {
      "cve": "CVE-2026-62654",
      "cwe": {
        "id": "CWE-494",
        "name": "Download of Code Without Integrity Check"
      },
      "notes": [
        {
          "category": "description",
          "text": "A special maintenance mode can be activated via a physical key sequence during device boot, in which the device downloads and executes program code from a network server without verifying its authenticity or integrity. This could allow an attacker with physical access to the device to upload and execute arbitrary, unsigned code.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "known_affected": [
          "1"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to V2.70 or later version",
          "product_ids": [
            "1"
          ],
          "url": "https://support.industry.siemens.com/cs/ww/en/view/109772413/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1"
          ]
        }
      ],
      "title": "CVE-2026-62654"
    }
  ]
}