| Publication Date: |
|
| Last Update: |
|
| Current Version: | V1.0 |
| CVSS v3.1 Base Score: | 7.5 |
| CVSS v4.0 Base Score: | 8.7 |
| Affected Product and Versions | Remediation |
|---|---|
|
All versions affected by CVE-2025-40944 |
Currently no fix is planned
|
|
|
|
|
All versions affected by CVE-2025-40944 |
Currently no fix is planned
|
|
All versions < V1.3 affected by CVE-2025-40944 |
Update to V1.3 or later version
|
|
All versions < V6.0.1 affected by CVE-2025-40944 |
Update to V6.0.1 or later version
|
|
|
|
|
All versions < V4.2.2 affected by CVE-2025-40944 |
Update to V4.2.2 or later version
|
|
All versions affected by CVE-2025-40944 |
Currently no fix is planned
|
|
|
Siemens has identified the following specific mitigations that customers can apply to reduce the risk:
Product-specific remediations or mitigations can be found in the section
Known Affected Products.
Please follow the General Security Recommendations.
As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity
This chapter describes all vulnerabilities (CVE-IDs) addressed in this security advisory. Wherever applicable, it also documents the product-specific impact of the individual vulnerabilities.
Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state.
This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
| CVSS v3.1 Base Score | 7.5 |
| CVSS v3.1 Vector | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
| CVSS v4.0 Base Score | 8.7 |
| CVSS v4.0 Vector | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N |
| CWE | CWE-400: Uncontrolled Resource Consumption |
| V1.0 (2026-01-13): | Publication Date |