Publication Date:
Last Update:
Current Version: V1.3
CVSS v3.1 Base Score: 6.5
CVSS v4.0 Base Score: 7.1
Un-/Collapse All
Affected Product and Versions Remediation

All versions
affected by all CVEs
Currently no fix is available
The vulnerability is fixed if SIMATIC WinCC V7.5 SP2 Update 15 or later version is installed on the same system

All versions
affected by all CVEs
Currently no fix is available
The vulnerability is fixed if SIMATIC WinCC V7.5 SP2 Update 15 or later version is installed on the same system

All versions
affected by all CVEs
Currently no fix is available
Update to V9.1 SP2; then update SIMATIC WinCC to V7.5 SP2 Update 15 or later version

All versions
affected by all CVEs
Currently no fix is available
The vulnerability is fixed if SIMATIC WinCC V7.5 SP2 Update 15 or later version is installed on the same system

All versions < V18 Update 4
affected by all CVEs
Update to V18 Update 4 or later version

All versions < V19 Update 2
affected by all CVEs
Update to V19 Update 2 or later version

All versions
affected by all CVEs
Currently no fix is planned

All versions < V7.5 SP2 Update 15
affected by all CVEs
Update to V7.5 SP2 Update 15 or later version

All versions < V8.0 Update 4
affected by all CVEs
Update to V8.0 Update 4 or later version
  • Ensure that SIMATIC WinCC, SIMATIC WinCC Runtime Professional and SIMATIC PCS 7 stations communicate via encrypted channels (i.e. activate feature “Encrypted Communication” in SIMATIC WinCC and SIMATIC PCS 7). Enabling “Encrypted Communication” completely mitigates the vulnerability

Product-specific remediations or mitigations can be found in the section Affected Products and Solution.
Please follow the General Security Recommendations.

As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity

Un-/Collapse All

This chapter describes all vulnerabilities (CVE-IDs) addressed in this security advisory. Wherever applicable, it also documents the product-specific impact of the individual vulnerabilities.

CVSS v3.1 Base Score 6.5
CVSS v3.1 Vector CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C
CVSS v4.0 Base Score 7.1
CVSS v4.0 Vector CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
CWE CWE-476: NULL Pointer Dereference
CVSS v3.1 Base Score 6.5
CVSS v3.1 Vector CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C
CVSS v4.0 Base Score 7.1
CVSS v4.0 Vector CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N
CWE CWE-476: NULL Pointer Dereference

  • Yu Cong from EZVIZ for reporting and coordinated disclosure

https://www.siemens.com/cert/advisories
V1.0 (2024-02-13): Publication Date
V1.1 (2024-04-09): Added a mitigation
V1.2 (2024-06-11): Added fix for SIMATIC WinCC Runtime Professional V19 and corrected fix version of WinCC V8.0 from SP4 to Update4
V1.3 (2024-07-09): Added fix for SIMATIC WinCC Runtime Professional V18