-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA512 # SSA-310688: Denial-of-Service Vulnerability in SIMATIC S7-1500 CPU Publication Date: 2014-08-14 Last Update: 2020-02-10 Current Version: 1.1 CVSS v3.1 Base Score: 7.5 SUMMARY ======= The latest firmware update for the SIMATIC S7-1500 CPU family fixes a vulnerability which could allow an attacker to perform a Denial-of-Service attack under certain conditions. The attacker must have network access to the device to exploit this vulnerability. AFFECTED PRODUCTS AND SOLUTION ============================== * SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) - Affected versions: All versions < V1.6 - Remediation: Update to V1.6 - Download: http://support.automation.siemens.com/WW/view/en/98164677 WORKAROUNDS AND MITIGATIONS =========================== Siemens has not identified any specific mitigations or workarounds. GENERAL SECURITY RECOMMENDATIONS ================================ As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity PRODUCT DESCRIPTION =================== Products of the SIMATIC S7-1500 CPU family have been designed for discrete and continuous control in industrial environments such as manufacturing, food and beverages, and chemical industries worldwide. SIPLUS extreme products are designed for reliable operation under extreme conditions and are based on SIMATIC, LOGO!, SITOP, SINAMICS, SIMOTION, SCALANCE or other devices. SIPLUS devices use the same firmware as the product they are based on. VULNERABILITY CLASSIFICATION ============================ The vulnerability classification has been performed by using the CVSS scoring system in version 3.1 (CVSS v3.1) (https://www.first.org/cvss/). The CVSS environmental score is specific to the customer's environment and will impact the overall CVSS score. The environmental score should therefore be individually defined by the customer to accomplish final scoring. An additional classification has been performed using the CWE classification, a community-developed list of common software security weaknesses. This serves as a common language and as a baseline for weakness identification, mitigation, and prevention efforts. A detailed list of CWE classes can be found at: https://cwe.mitre.org/. * Vulnerability CVE-2014-5074 Specially crafted TCP packets could cause a Denial-of-Service of the device if sent in a specific order. The CPU will automatically restart and remain in STOP mode. The CPU needs to be manually put into RUN mode again. CVSS v3.1 Base Score: 7.5 CVSS Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CWE: CWE-730: OWASP Top Ten 2004 Category A9 - Denial of Service ACKNOWLEDGMENTS =============== Siemens thanks the following parties for their efforts: * Arnaud Ebalard from Agence Nationale de la Sécurité des Systèmes d’Information (ANSSI) for coordination efforts * Artem Zinenko from Kaspersky for pointing out that SIPLUS should also be mentioned ADDITIONAL INFORMATION ====================== For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories HISTORY DATA ============ V1.0 (2014-08-14): Publication Date V1.1 (2020-02-10): SIPLUS devices now explicitly mentioned in the list of affected products TERMS OF USE ============ Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use. -----BEGIN PGP SIGNATURE----- iQIcBAEBCgAGBQJeQJ0AAAoJENP0geoRSq/kGjUP/2TvveCu3h65x/D8i5Q64XG8 gfK9sAEquVgH5Ygu+GSyYFDERcH/O4zTGKDwCOxKx5Jjqnw41unJGp9UMqwDWuU7 3D8Rn/F13sUJ6FZXBQX8u93azkpsXKhx2uR9zz+0PSZvgJhHIw8HhJaarAa84iQw bLB8VZ3t9XDHVpWfDxADp4+djNKmxK8xtbZBb7dY3fMdWOYcPkvuVM6hpdudo+M1 z+TzK8BZaNGF7q627Rjv/QpD/1bcMGVczlUy6uBAHWWT9ONaUMNBdQnjNtYjzrRw KCoamRBPv+ozJ2aYPmsj3zZpHXC0BCSbJ5SnNjahUaWUDSYWdE/pIpQ13BmYp361 TdO7orBaKr3brPGp1z5EmmbrSUpFDt8Dp2RKh3GVV8ev+eSyE3CbF/HsH0OG23RA CJHfv2loexONp+eoG84thhMfiWNgEGEf0pAm2ILEi4dzC1jwreccI6mQiiVCgN0S sdWV+0rh/yVAL1+eUbxiugaOoo2YrtAscuHBFMkDXZS0L4SFVROzGGHY/Xi3M2ay SfVwMZlCjievMj+U8d+jU6WB5YCfoca3/l53mpz8DFfeQuU1r042pQXQIPaYoiRV hLmNsWX3c9BFH4YwaUa2D0KdUNPhTlrMXhPVCBuIA3R+Lx5khrE2iOL/D6Bv/aCd BfS6SmO5+zGAKK5cmmRm =WtOI -----END PGP SIGNATURE-----