-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA512 # SSA-346262: Denial-of-Service in Industrial Products Publication Date: 2017-11-23 Last Update: 2022-02-08 Current Version: 3.2 CVSS v3.1 Base Score: 7.5 SUMMARY ======= Several industrial products are affected by a vulnerability that could allow remote attackers to conduct a Denial-of-Service (DoS) attack by sending specially crafted packets to port 161/udp (SNMP). Siemens has released updates for several affected products, and recommends that customers update to the new version. Siemens is preparing further updates and recommends specific countermeasures until patches are available. AFFECTED PRODUCTS AND SOLUTION ============================== * Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller - Affected versions: All versions < V4.1.1 Patch 05 - Remediation: Update to V4.1.1 Patch 05 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109755160 * Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200 - Affected versions: All versions < V4.5 - Remediation: Update to V4.5 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109755151 * Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P - Affected versions: All versions < V4.5 - Remediation: Update to V4.5 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109750012 * SIMATIC Compact Field Unit - Affected versions: All versions - Remediation: Currently no remediation is available See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200AL - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 4AO U/I 4xM12 (6ES7145-6HD00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8 DIO, DC24V/1,3A, 8xM12 (6ES7147-6BG00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8 DO, DC24V/2A, 8xM12 (6ES7142-6BR00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8AI RTD/TC 8xM12 (6ES7144-6KD50-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8AI; 4 U/I; 4 RTD/TC 8xM12 (6ES7144-6KD00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8DI, DC24V, 4xM12 (6ES7141-6BF00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8DI, DC24V, 8xM12 (6ES7141-6BG00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8DO, DC24V/0,5A, 4xM12 (6ES7142-6BF50-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 4xM12 (6ES7142-6BF00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 8DO, DC24V/1,3A, 8xM12 (6ES7142-6BG00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 16DI, DC24V, 8xM12 (6ES7141-6BH00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN, 16DO DC24V/1,3A, 8xM12 (6ES7142-6BH00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200ecoPN: IO-Link Master (6ES7148-6JA00-0AB0) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200M (incl. SIPLUS variants) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200MP IM155-5 PN BA (incl. SIPLUS variants) - Affected versions: All versions < V4.0.2 - Remediation: Update to V4.0.2 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109754281 * SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants) - Affected versions: All versions < V4.2 - Remediation: Update to V4.2 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/us/en/view/93012181 * SIMATIC ET200MP IM155-5 PN ST (incl. SIPLUS variants) - Affected versions: All versions < V4.1 - Remediation: Update to V4.1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/78647504 * SIMATIC ET200pro - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200S (incl. SIPLUS variants) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200SP IM155-6 PN BA (incl. SIPLUS variants) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants) - Affected versions: All versions < V1.1.0 - Remediation: Update to V1.1.0 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109763483 * SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants) - Affected versions: All versions < V4.2.0 - Remediation: Update to V4.2.0 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/85624387 * SIMATIC ET200SP IM155-6 PN HS (incl. SIPLUS variants) - Affected versions: All versions < V4.0.1 - Remediation: Update to V4.0.1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109795369 * SIMATIC ET200SP IM155-6 PN ST (incl. SIPLUS variants) - Affected versions: All versions - Remediation: Currently no remediation is planned See recommendations from section "Workarounds and Mitigations" * SIMATIC PN/PN Coupler (incl. SIPLUS NET variants) - Affected versions: All versions < V4.2.0 - Remediation: Update to V4.2.0 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109760973 * SIMATIC S7-200 SMART - Affected versions: All versions < V2.03.01 - Remediation: Update to V2.03.01 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/cn/en/view/109749409 * SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) - Affected versions: All versions < V3.X.16 - Remediation: Update to V3.X.16 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/ps/13752/dl * SIMATIC S7-400 H V6 CPU family and below (incl. SIPLUS variants) - Affected versions: All versions < V6.0.8 - Remediation: Update to V6.0.8 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109474550 * SIMATIC S7-400 PN/DP V6 CPU family and below (incl. SIPLUS variants) - Affected versions: All versions < V6.0.6 - Remediation: Update to V6.0.6 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/de/en/view/109474874 * SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) - Affected versions: All versions < V7.0.2 - Remediation: Update to V7.0.2 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109752685 * SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) - Affected versions: All versions < V8.2.1 - Remediation: Update to V8.2.1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109476571 * SIMATIC S7-1200 CPU family (incl. SIPLUS variants) - Affected versions: All versions < V4.2.3 - Remediation: Update to V4.2.3 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/us/en/view/109741461 * SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) - Affected versions: All versions < V2.0 - Remediation: Upgrade to V2.0 or newer See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/us/en/ps/13717/dl * SIMATIC S7-1500 Software Controller - Affected versions: All versions < V2.0 - Remediation: Upgrade to V2.0 or newer See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/us/en/view/109478528 * SIMATIC TDC CP51M1 - Affected versions: All versions < V1.1.8 - Remediation: Update to V1.1.8 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/27049282 * SIMATIC TDC CPU555 - Affected versions: All versions < V1.1.1 - Remediation: Update to V1.1.1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109740119 * SIMATIC WinAC RTX (F) 2010 - Affected versions: All versions < SIMATIC WinAC RTX 2010 SP3 - Remediation: Update to SIMATIC WinAC RTX 2010 SP3 and apply BIOS and Microsoft Windows updates See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109765109 * SIMOCODE pro V PN (incl. SIPLUS variants) - Affected versions: All versions < V2.1.1 - Remediation: Update to V2.1.1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109749989 * SIMOTION C - Affected versions: All versions < V5.1 HF1 - Remediation: Update to V5.1 HF1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/31263919 * SIMOTION D (incl. SIPLUS variants) - Affected versions: All versions < V5.1 HF1 - Remediation: Update to V5.1 HF1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/31045047 * SIMOTION P V4.4 and V4.5 - Affected versions: All versions < V4.5 HF5 - Remediation: Update to V4.5 HF5 See further recommendations from section "Workarounds and Mitigations" - Download: Please contact your Siemens representative for information on how to obtain the update. * SIMOTION P V5 - Affected versions: All versions < V5.1 HF1 - Remediation: Update to V5.1 HF1 See further recommendations from section "Workarounds and Mitigations" - Download: Please contact your Siemens representative for information on how to obtain the update. * SINAMICS DCM w. PN - Affected versions: All versions < V1.4 SP1 HF6 - Remediation: Update to V1.4 SP1 HF6 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/44029688 * SINAMICS DCP w. PN - Affected versions: All versions < V1.2 HF2 - Remediation: Update to V1.2 HF2 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109474935 * SINAMICS G110M w. PN - Affected versions: All versions < V4.7 SP9 HF1 - Remediation: Update to V4.7 SP9 HF1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/document/109750507 * SINAMICS G120(C/P/D) w. PN (incl. SIPLUS variants) - Affected versions: All versions < V4.7 SP9 HF1 - Remediation: Update to V4.7 SP9 HF1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/document/109750507 * SINAMICS G130 V4.7 w. PN - Affected versions: All versions < V4.7 HF29 - Remediation: Update to V4.7 HF29 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/103433117 * SINAMICS G130 V4.8 w. PN - Affected versions: All versions < V4.8 HF4 - Remediation: Update to V4.8 HF4 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109742040 * SINAMICS G150 V4.7 w. PN - Affected versions: All versions < V4.7 HF29 - Remediation: Update to V4.7 HF29 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/103433117 * SINAMICS G150 V4.8 w. PN - Affected versions: All versions < V4.8 HF4 - Remediation: Update to V4.8 HF4 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109742040 * SINAMICS S110 w. PN - Affected versions: All versions < V4.4 SP3 HF6 - Remediation: Update to V4.4 SP3 HF6 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/document/109474320 * SINAMICS S120 prior to V4.7 w. PN (incl. SIPLUS variants) - Affected versions: All versions < V4.7 - Remediation: Update to latest version of V5.1 SP1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/document/109758423 * SINAMICS S120 V4.7 SP1 w. PN (incl. SIPLUS variants) - Affected versions: All versions - Remediation: Update to latest version of V5.1 SP1 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/document/109758423 * SINAMICS S120 V4.7 w. PN (incl. SIPLUS variants) - Affected versions: All versions < V4.7 HF29 - Remediation: Update to V4.7 HF29 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/92522512 * SINAMICS S120 V4.8 w. PN (incl. SIPLUS variants) - Affected versions: All versions < V4.8 HF5 - Remediation: Update to V4.8 HF5 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/us/en/view/109740193 * SINAMICS S150 V4.7 w. PN - Affected versions: All versions < V4.7 HF29 - Remediation: Update to V4.7 HF29 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/103433117 * SINAMICS S150 V4.8 w. PN - Affected versions: All versions < V4.8 HF4 - Remediation: Update to V4.8 HF4 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109742040 * SINAMICS V90 w. PN - Affected versions: All versions < V1.02 - Remediation: Update to V1.02 See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/document/109746210 * SINUMERIK 840D sl - Affected versions: All versions < V4.8 SP3 - Remediation: Update to V4.8 SP3 See further recommendations from section "Workarounds and Mitigations" - Download: The update can be obtained from your local service organization. * SIRIUS Soft Starter 3RW44 PN - Affected versions: All versions - Remediation: Currently no remediation is available See recommendations from section "Workarounds and Mitigations" WORKAROUNDS AND MITIGATIONS =========================== Siemens has identified the following specific workarounds and mitigations that customers can apply to reduce the risk: * Disable SNMP if this is supported by the product (refer to the product documentation). Disabling SNMP fully mitigates the vulnerability. * Protect network access to port 161/udp of affected devices. * Apply cell protection concept and implement Defense-in-Depth: https://www.siemens.com/cert/operational-guidelines-industrial-security. * Use VPN for protecting network communication between cells. GENERAL SECURITY RECOMMENDATIONS ================================ As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity PRODUCT DESCRIPTION =================== Development/Evaluation Kits for PROFINET IO are used to develop compact or modular PROFINET field devices. PN/PN coupler is used for connecting two PROFINET networks. Siemens SIMATIC S7-300 CPU families, S7-400 CPU families, S7-1200 CPU families, and S7-1500 CPU families have been designed for discrete and continuous control in industrial environments such as manufacturing, food and beverages, and chemical industries worldwide. SIMATIC ET 200 Interface modules for PROFINET IO are used to connect field devices (IO Devices) to controllers (IO Controller) via PROFINET. SIMATIC S7-1500 Software Controller is a SIMATIC software controller for PC-based automation solutions. SIMATIC TDC is a multiprocessor automation system for drive, control and technology tasks. The system is used particularly for large plants. SIMATIC WinAC RTX (F) 2010 is a SIMATIC software controller for PC-based automation solutions. SIMOCODE is the flexible and modular motor management system for low-voltage motors. SIMOTION is a scalable high performance hardware and software system for motion control. SINUMERIK CNC offers automation solutions for the shop floor, job shops and large serial production environments. SIPLUS extreme products are designed for reliable operation under extreme conditions and are based on SIMATIC, LOGO!, SITOP, SINAMICS, SIMOTION, SCALANCE or other devices. SIPLUS devices use the same firmware as the product they are based on. SIRIUS 3RW soft starters permit soft starting and soft rampdown of three-phase asynchronous motors. The S7-200 SMART series is a line of micro-programmable logic controllers that can control a variety of small automation applications. The SIMATIC Compact Field Unit is a field unit for use as an IO device on the PROFINET IO network of an automation system. The SINAMICS converter family is used to control a wide variety of drives, especially in mechanical engineering and plant construction. VULNERABILITY CLASSIFICATION ============================ The vulnerability classification has been performed by using the CVSS scoring system in version 3.1 (CVSS v3.1) (https://www.first.org/cvss/). The CVSS environmental score is specific to the customer's environment and will impact the overall CVSS score. The environmental score should therefore be individually defined by the customer to accomplish final scoring. An additional classification has been performed using the CWE classification, a community-developed list of common software security weaknesses. This serves as a common language and as a baseline for weakness identification, mitigation, and prevention efforts. A detailed list of CWE classes can be found at: https://cwe.mitre.org/. * Vulnerability CVE-2017-12741 Specially crafted packets sent to port 161/udp could cause a Denial-of-Service condition. The affected devices must be restarted manually. CVSS v3.1 Base Score: 7.5 CVSS Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C CWE: CWE-400: Uncontrolled Resource Consumption ACKNOWLEDGMENTS =============== Siemens thanks the following parties for their efforts: * Artem Zinenko from Kaspersky for pointing out that SIPLUS should also be mentioned * George Lashenko from CyberX for coordinated disclosure of the vulnerability ADDITIONAL INFORMATION ====================== For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories HISTORY DATA ============ V1.0 (2017-11-23): Publication Date V1.1 (2017-12-18): Changed affected products: V2.0 and newer of SIMATIC S7-1500 and V2.0 and newer of SIMATIC S7-1500 Software Controller are not affected. Added update information for SIMATIC S7-400 H V6 V1.2 (2018-01-18): New advisory format, added update information for SINAMICS V90 w. PN, SINAMICS S120 and SINAMICS S110 w. PN V1.3 (2018-01-24): Added update for S7-400 V7 and SIMATIC ET 200MP IM155-5 PN BA V1.4 (2018-02-22): Added update for SIMATIC ET 200MP IM155-5 PN ST, SIMOTION P V4.4 and V4.5, and Development/Evaluation Kits for PROFINET IO DK Standard Ethernet Controller and EK-ERTEC 200, Corrected patch link for SIMOTION D V1.5 (2018-05-03): Added update information for V4.8 of SINAMICS G130, G150, S120 and S150 V1.6 (2018-05-15): Added update information for V4.7 of SINAMICS G130, G150, S120 and S150 V1.7 (2018-09-11): Added update for SINAMICS DCP w. PN and SINAMICS DCM w. PN V1.8 (2018-10-09): Added update for SIMATIC S7-1200 CPU V1.9 (2018-11-13): Updated solution for SINAMICS S120, added solution for PN/PN Coupler, SIMATIC ET200 SP, SIMATIC S7-400 V8, SIMOCODE pro V PROFINET V2.0 (2018-12-11): Updated solution for SIMATIC ET 200MP IM155-5 PN HF V2.1 (2019-01-08): Updated solution for SIMATIC S7-300 V2.2 (2019-02-12): Updated solution for SIMATIC ET 200SP IM155-6 PN HA V2.3 (2019-03-12): Update for SINUMERIK 840D sl V2.4 (2019-10-08): Renamed SIMATIC WinAC RTX 2010 incl. F to SIMATIC WinAC RTX (F) 2010 and added update information for SIMATIC WinAC RTX (F) 2010 V2.5 (2020-02-10): SIPLUS devices now explicitly mentioned in the list of affected products V2.6 (2020-04-14): Mention that SIMATIC S7-400 CPU family below V6 is vulnerable V2.7 (2020-07-14): Added SIMATIC TDC CP51M1 and CPU555 to the list of affected products V2.8 (2020-08-11): Added SIMATIC ET200ecoPN product variants (MLFB IDs) that are not affected V2.9 (2021-03-09): Added ecoPN model (6ES7148-6JG00-0BB0) as not affected V3.0 (2021-06-08): Updated solution for SIMATIC ET200SP IM155-6 PN HS V3.1 (2021-10-12): Clarified affected ET200ecoPN models V3.2 (2022-02-08): Clarified that no remediation is planned for ET200 devices TERMS OF USE ============ Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use. -----BEGIN PGP SIGNATURE----- iQIzBAEBCgAdFiEEHyx/myPwjH9jB9tDlm7gTEmyujQFAmIBsoAACgkQlm7gTEmy ujRbOhAAy1eyswuTMowk8WnJUsNUpR0Vwp+F5U8kV2wnJ4RF2lxS/h5cm6CJg1nq YFvoBlAEitlTEsNu2OT8S/8cQAlYiaTfJ3xY0G06MMoqu46fcmhoal2oa8U5VDAz wWvG5EBKZnX94BBRWg+OD4dhDPNptIR2CRqOmMlXeLbRn7WXy89binL0MBS3Bozx 36+CJ69CMBrh1fw6RudvvsJCctBSh7tqKEnALhoebo1c+cJ62WEsNkZgdNORc+GZ ZiY1GoU2VE4yFQiAz+fEQs+3G5lpnDWZr1Gy8ZkUdHs3wSlSokaU+EIV6OCN8Ntx GkSNJ0efIR/CVhCleZpa78GCvkkS21NQi3Km8rLQjKB0V7dsOlLQPQ7n6whg9I64 gx0CpKHtdWeL0TqlwFnGX83l19VALw6z4K7RHMEsMzBbIpcmZqLQjoUNsHHI0U0+ Bi+YQnN/nfLJCiKvpIw6rkk0pyH2d1lbqsAoBjB0z7iJOLgWJgN1v2APnCoIJSBh NDjOvH/QkalD+LpY6UovNLkI0MlbTh1nz0ExRsc0PdPO6ON1xQegtbLLTmhsbqr3 moPEr3wra532Hmg6wUuRVNSNbhO+ATA/eWPdT7fUeKyn2t5x+QtuWSWQi7H/D+Df bKo5UUb01hfpdMayYMZ3bZ3CidAZYgkjuMYtCgFvSGWVyJRqMFA= =jqhZ -----END PGP SIGNATURE-----