-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA512 # SSA-649853: Improper Certificate Validation Vulnerability in Industrial Edge Management Publication Date: 2022-10-11 Last Update: 2022-10-11 Current Version: 1.0 CVSS v3.1 Base Score: 7.4 SUMMARY ======= Industrial Edge Management contains a vulnerability that could allow an unauthenticated attacker to spoof a trusted entity by interfering in the communication path between the Industrial Edge Management (IEM) and the Industrial Edge Hub (IEH) using a crafted certificate. An attacker could use this to inject malicious maintenance requests (e.g. sending statistics, activating remote support, exchanging the initial keys when onboarding, querying new extensions). Siemens has released an update for the Industrial Edge Management and recommends to update to the latest version. AFFECTED PRODUCTS AND SOLUTION ============================== * Industrial Edge Management - Affected versions: All versions < V1.5.1 - Remediation: Update to V1.5.1 or later version - Download: https://iehub.eu1.edge.siemens.cloud/ WORKAROUNDS AND MITIGATIONS =========================== Product-specific remediations or mitigations can be found in the section "Affected Products and Solution". Please follow the "General Security Recommendations". GENERAL SECURITY RECOMMENDATIONS ================================ As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial- security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity PRODUCT DESCRIPTION =================== Industrial Edge Management (IEM) enables a centralized management of Siemens Industrial Edge Devices and Edge Applications. IEM is tailored to customer’s needs and is operated by the customer (on-premises). VULNERABILITY CLASSIFICATION ============================ The vulnerability classification has been performed by using the CVSS scoring system in version 3.1 (CVSS v3.1) (https://www.first.org/cvss/). The CVSS environmental score is specific to the customer's environment and will impact the overall CVSS score. The environmental score should therefore be individually defined by the customer to accomplish final scoring. An additional classification has been performed using the CWE classification, a community-developed list of common software security weaknesses. This serves as a common language and as a baseline for weakness identification, mitigation, and prevention efforts. A detailed list of CWE classes can be found at: https://cwe.mitre.org/. * Vulnerability CVE-2022-40147 The affected software does not properly validate the server certificate when initiating a TLS connection. This could allow an attacker to spoof a trusted entity by interfering in the communication path between the client and the intended server. CVSS v3.1 Base Score: 7.4 CVSS Vector: CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:N/E:P/RL:O/RC:C CWE: CWE-295: Improper Certificate Validation ADDITIONAL INFORMATION ====================== For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories HISTORY DATA ============ V1.0 (2022-10-11): Publication Date TERMS OF USE ============ Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use. Copyright: Siemens 2022 -----BEGIN PGP SIGNATURE----- iQIzBAEBCgAdFiEEHyx/myPwjH9jB9tDlm7gTEmyujQFAmNEsgAACgkQlm7gTEmy ujQwThAAituWecOYbELfmpOfZti21SLWig1yBG1t+Yde90sm6LuMkh8GfEaeT7pw RlwlvAIeTQEbkrw/7Id4L+Je1ERtMLbuZRjYa/yw2fOGR+6H2f6670wryK2oqTEi AYBRVytbYR009czZ3JS0Csk4GtQohAsh8g0v+ohrA/iwHxXbotIBr+PIgIcrxNZM WY3a3FkyRcHtlCnroMbt91kcaxnP4QobUG6Di1OAnfFG22q4iBfETrwzuOOIW+pu 5qbESIsbTPyDc9JoxaRZCAMSWDJ4ew/Tgg48bfEVm7OTMVVr62IeRtXvweymz8r9 gRH3nfXqtML/64WlqqltSAv0fGPaykf6QowrY2eVUWutv0vFbLA38Urbx5nVOy1B JYSRcvgo5oxNGFFnkguHt2VJKPEw/klJa4nl8ysq3rawymqgz6JMKtBeJaYPk75s bXKlgk9R5ttkWLuPnM/UvtrV5EVooTCD5NmSyM1/81HDCqftjKMODbnKg9BQR4Jo qnvVDkRFWgoad7IhzGuZ37uXa/cnQODkTs8g26jVL6XhDkPhO3czfpc33d82/tW1 wr8cPKFhD6cTxvpgsc+1zo/l5sLoiWxM/mXHgnfaze9+Tz7KZhN4uxzQAgldJj89 qyL1qtgqvL5cKZz7XDTzYpO+LPnidQmFCUsua3qz80VTfUX3s0s= =3Jpb -----END PGP SIGNATURE-----