-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA512 # SSA-750499: Weak Encryption Vulnerability in SIPROTEC 5 Devices Publication Date: 2024-07-09 Last Update: 2024-08-13 Current Version: 1.1 CVSS v3.1 Base Score: 5.9 CVSS v4.0 Base Score: 8.2 SUMMARY ======= The SIPROTEC 5 devices are supporting weak encryption. This could allow an unauthorized attacker in a man-in-the-middle position to read any data passed over the connection between legitimate clients and the affected device. Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is preparing further fix versions and recommends specific countermeasures for products where fixes are not, or not yet available. AFFECTED PRODUCTS AND SOLUTION ============================== * SIPROTEC 5 - CP050 Devices: - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109796884/ * SIPROTEC 5 Compact 7SX800 (CP050): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109796884/ * SIPROTEC 5 - CP100 Devices: - Remediation: See below See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SA82 (CP100): - Affected versions: All versions - Remediation: Currently no fix is available See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SD82 (CP100): - Affected versions: All versions - Remediation: Currently no fix is available See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SJ81 (CP100): - Affected versions: All versions < V8.89 - Remediation: Update to V8.89 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109751934/ * SIPROTEC 5 7SJ82 (CP100): - Affected versions: All versions < V8.89 - Remediation: Update to V8.89 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109751934/ * SIPROTEC 5 7SK82 (CP100): - Affected versions: All versions < V8.89 - Remediation: Update to V8.89 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757434/ * SIPROTEC 5 7SL82 (CP100): - Affected versions: All versions - Remediation: Currently no fix is available See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7UT82 (CP100): - Affected versions: All versions - Remediation: Currently no fix is available See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 - CP150 Devices: - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SA82 (CP150): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SD82 (CP150): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SJ81 (CP150): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109751934/ * SIPROTEC 5 7SJ82 (CP150): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109751934/ * SIPROTEC 5 7SK82 (CP150): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757434/ * SIPROTEC 5 7SL82 (CP150): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SX82 (CP150): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109768011/ * SIPROTEC 5 7UT82 (CP150): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757438/ * SIPROTEC 5 - CP200 Devices: - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 6MD85 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 6MD86 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7KE85 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SA84 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SA86 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SA87 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SD84 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SD86 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SD87 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SJ85 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SJ86 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SK85 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SL86 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SL87 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7SS85 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7ST85 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7UT85 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7UT86 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7UT87 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 7VK87 (CP200): - Affected versions: All versions - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 - CP300 Devices: - Remediation: See below See further recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 6MD84 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109814150/ * SIPROTEC 5 6MD85 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757428/ * SIPROTEC 5 6MD86 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757428/ * SIPROTEC 5 6MD89 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109742950/ * SIPROTEC 5 6MU85 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109765263/ * SIPROTEC 5 7KE85 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757430/ * SIPROTEC 5 7SA86 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SA87 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SD86 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SD87 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SJ85 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109751934/ * SIPROTEC 5 7SJ86 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SK85 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757434/ * SIPROTEC 5 7SL86 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SL87 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7SS85 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757429/ * SIPROTEC 5 7ST85 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109740299/ * SIPROTEC 5 7ST86 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109768428/ * SIPROTEC 5 7SX85 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109768011/ * SIPROTEC 5 7UM85 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757431/ * SIPROTEC 5 7UT85 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757438/ * SIPROTEC 5 7UT86 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757438/ * SIPROTEC 5 7UT87 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757438/ * SIPROTEC 5 7VE85 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109749865/ * SIPROTEC 5 7VK87 (CP300): - Affected versions: All versions < V9.65 - Remediation: Update to V9.65 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109757433/ * SIPROTEC 5 7VU85 (CP300): - Affected versions: All versions < V9.64 - Remediation: Update to V9.64 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109800399/ * SIPROTEC 5 Communication Modules: - Remediation: See below See further recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1): - Remediation: See below See further recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1): - Affected versions: All versions installed on CP200 devices - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1): - Affected versions: All versions < V8.89 installed on CP100 devices - Remediation: Update to V8.89 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109740816/ * SIPROTEC 5 Communication Module ETH-BA-2EL (Rev.1): - Affected versions: All versions < V9.62 installed on CP150 and CP300 devices - Remediation: Update to V9.62 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109740816/ * SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1): - Remediation: See below See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1): - Affected versions: All versions installed on CP200 devices - Remediation: Currently no fix is planned See recommendations from section "Workarounds and Mitigations" * SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1): - Affected versions: All versions < V8.89 installed on CP100 devices - Remediation: Update to V8.89 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109740816/ * SIPROTEC 5 Communication Module ETH-BB-2FO (Rev. 1): - Affected versions: All versions < V9.62 installed on CP150 and CP300 devices - Remediation: Update to V9.62 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109740816/ * SIPROTEC 5 Communication Module ETH-BD-2FO: - Affected versions: All versions < V9.62 - Remediation: Update to V9.62 or later version See further recommendations from section "Workarounds and Mitigations" - Download: https://support.industry.siemens.com/cs/ww/en/view/109740816/ WORKAROUNDS AND MITIGATIONS =========================== Siemens has identified the following specific workarounds and mitigations that customers can apply to reduce the risk: * Restrict access to port 443/tcp for web, 4443/tcp for DIGSI 5 and configurable port for syslog over TLS to trusted IP addresses only Product-specific remediations or mitigations can be found in the section "Affected Products and Solution". Please follow the "General Security Recommendations". GENERAL SECURITY RECOMMENDATIONS ================================ Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines can be found at: https://www.siemens.com/gridsecurity PRODUCT DESCRIPTION =================== SIPROTEC 5 devices provide a range of integrated protection, control, measurement, and automation functions for electrical substations and other fields of application. VULNERABILITY DESCRIPTION ========================= This chapter describes all vulnerabilities (CVE-IDs) addressed in this security advisory. Wherever applicable, it also documents the product-specific impact of the individual vulnerabilities. * Vulnerability CVE-2024-38867 The affected devices are supporting weak ciphers on several ports (443/tcp for web, 4443/tcp for DIGSI 5 and configurable port for syslog over TLS). This could allow an unauthorized attacker in a man- in-the-middle position to decrypt any data passed over to and from those ports. CVSS v3.1 Base Score: 5.9 CVSS Vector: CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N CVSS v4.0 Base Score: 8.2 CVSS Vector: CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N CWE: CWE-326: Inadequate Encryption Strength ACKNOWLEDGMENTS =============== Siemens thanks the following party for its efforts: * Hydro-Québec for coordinated disclosure of CVE-2024-38867 ADDITIONAL INFORMATION ====================== For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories HISTORY DATA ============ V1.0 (2024-07-09): Publication Date V1.1 (2024-08-13): Updating the CVE description TERMS OF USE ============ Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use. Copyright: Siemens 2024 -----BEGIN PGP SIGNATURE----- iQIzBAEBCgAdFiEEch+g+vCfo0skv7l6x5aGHHWng/oFAma6ogAACgkQx5aGHHWn g/roNw/+IiP175O0VInGKU9WJbLp+PYntwTreLoVI+OUIH2muovSzt0oGLU3ZEV5 yaqDe3EgCGceTx34jPuvyS7wGzo2ksnsqO+ezUAqE4Kj3QbCZWFlDa0AdBYM5979 2EQDC1OtHA9v8uZsw5QdnyPdb9vdBeTbe5S98rNFvyYfFkm08BB2QOsBICWEkPAz U3z4gnqBF9fgDTJwoG0DVDETnEYSS3WfxACuewlOy9uYbHMWzoSunx1j6t0oEKda eSzjDonz/ZqU7GAQN+Is9ztctyyQBf9pd2p9E02OKLhsOBFRgHfayc+0JoEqgaGY AOZeNcxklbFi1IeFPKDSQhKw/4rSHX1EoYN7PpsUucfsIDehLYxli2sl74hBjK9K 8Ku+I7ntzgd9cmdRmHPIXgqN+vZkLvLgCp5WCx+DHQsD7W/tESHxtszRs5WExS6j Tahc+UdBO28VJ0HGrZ1wopQMPfEMhs0t0hBzh5Q0bb0pSJexfmc26XF4a8/YgqXD TgNJMYPV84sEiTVDPA8mWKZ/zic+k4mdm6KhMxznvwnMd39XPz+8wx+eMbVcuDKG 5JuZGbIuvJEBY3tvvPlJMrO+K1u1Lw0AikbFfidaJOL+BigVBvSD1NDREdr+ts3n gIQJ4KatHxZKL1Z0UPPY3pJF8EPcHqJeL/xKqiRFwfXJXLyzIDQ= =GsSC -----END PGP SIGNATURE-----