-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA512 # SSA-845879: Firmware Downgrade Vulnerability in EN100 Ethernet Communication Module for SIPROTEC 4, SIPROTEC Compact and Reyrolle Publication Date: 2018-03-08 Last Update: 2019-02-12 Current Version: 1.2 CVSS v3.0 Base Score: 7.5 SUMMARY ======= The EN100 Ethernet communication module, which is an optional extension for SIPROTEC 4, SIPROTEC Compact and Reyrolle devices, allows an unauthenticated upload of firmware updates to the communication module in affected versions. Siemens has released updates for several affected products, is working on updates for the remaining affected products, and recommends specific countermeasures until fixes are available. AFFECTED PRODUCTS AND SOLUTION ============================== SIPROTEC 4, SIPROTEC Compact and Reyrolle devices can be extended with an EN100 module. For customers who are currently using the discontinued EN100-E or EN100-O modules, Siemens recommends to upgrade to EN100-E+ or EN100-O+ modules in order to apply the firmware updates. * EN100 Ethernet module IEC 61850 variant - Affected versions: All versions < V4.30 - Remediation: Update to V4.30 and configure maintenance password - Download: https://support.industry.siemens.com/cs/us/en/view/109745821 * EN100 Ethernet module DNP3 variant - Affected versions: All versions < V1.04 - Remediation: Update to V1.04 and configure maintenance password - Download: https://support.industry.siemens.com/cs/us/en/view/109745821 * EN100 Ethernet module PROFINET IO variant - Affected versions: All versions - Remediation: See recommendations from section Workaround and Mitigations * EN100 Ethernet module Modbus TCP variant - Affected versions: All versions - Remediation: See recommendations from section Workaround and Mitigations * EN100 Ethernet module IEC 104 variant - Affected versions: All versions < V1.22 - Remediation: Update to V1.22 and configure maintenance password - Download: https://support.industry.siemens.com/cs/document/109745821 WORKAROUNDS AND MITIGATIONS =========================== Siemens has identified the following specific workarounds and mitigations that customers can apply to reduce the risk: * Apply secure substation concept and Defense-in-Depth (see https://www.siemens.com/gridsecurity) GENERAL SECURITY RECOMMENDATIONS ================================ As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines to Secure Substations can be found at: https://www.siemens.com/gridsecurity PRODUCT DESCRIPTION =================== The EN100 Ethernet modules are used for enabling process communication on either IEC 61850, PROFINET IO, Modbus TCP, DNP3 TCP or IEC 104 protocols via electrical/optical 100 Mbit interfaces on SIPROTEC 4, SIPROTEC Compact and Reyrolle devices. VULNERABILITY CLASSIFICATION ============================ The vulnerability classification has been performed by using the CVSS scoring system in version 3.0 (CVSS v3.0) (https://www.first.org/cvss/). The CVSS environmental score is specific to the customer's environment and will impact the overall CVSS score. The environmental score should therefore be individually defined by the customer to accomplish final scoring. * Vulnerability CVE-2018-4838 The web interface (TCP/80) of affected devices allows an unauthenticated user to upgrade or downgrade the firmware of the device, including to older versions with known vulnerabilities. CVSS v3.0 Base Score: 7.5 CVSS v3.0 Vector: CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N/E:P/RL:O/RC:C ACKNOWLEDGMENTS =============== Siemens thanks the following parties for their efforts: * Ilya Karpov and Alexey Stennikov from Positive Technologies for coordinated disclosure ADDITIONAL INFORMATION ====================== For further inquiries on vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories HISTORY DATA ============ V1.0 (2018-03-08): Publication Date V1.1 (2018-04-17): Added update for DNP3 TCP V1.2 (2019-02-12): Added update information for IEC 104 variant of EN100 module TERMS OF USE ============ Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use. -----BEGIN PGP SIGNATURE----- iQIzBAEBCgAdFiEEfwRu2jOObZSjqkl0u2eV6o5V1S4FAlxiDIAACgkQu2eV6o5V 1S4bjBAApa3yPMXyQKzD0NBOIwhevSEqEQXhxxra9X6fx9oszT/ihhlyVF64HwnP Hs55h7m/8ceNlbbtiyOJ43j4Z17UteHgtoRJx4+TFXxAD7iOYvFw1bDxMjhHlSib /vj8LCjOzrZV0jWH5ocTY5qiYWhU4FfgD+Rnjgx/iolooz06eTruNswhYl8IpYcL aQTP5dVIhr4+n+EC7B6946Ujk737DQAqz592jI65o+3HYmswWec8YyzE1nGuQ4a9 FGZfwSTQks5GiYm5JrwlAtH/EnrBUuKjBdSlM6tq405I2RwbKaFPYVCi5X9Yb1Mj LlnYFBfMq4Zw9aQSznRBrsvXTstfYS3uapP3tj5KZlwVVW8GQdt9VxNkiV3tfKO3 +q8vN1XqIgaW06HH3Z1AXk57EQ5nxKfMBt43e+gSpwvI3FkBR+ggceiXU8CpDj7K Dj9md3zJjJ3ZLzVwPx+QzGGU59O4cFfxq30X80YRpECAKmmB5u3uDSaGpfiqKJuF Pubk4A3wS4PAnqvE6udL+0ccvm3cXNRl7etfE0IzJ4dNWwFzz094pdR7vbeWnFz0 niYEtFlP4h53UJUqdkXw8Ux8COpz8O1BncpZMaWn5Q58iaqgh8UPGnYImN43PBEE SUhDMO59NHOPPdFX0xNLVcHyusR38jUWY2QAxXsh4tfxkL28KKY= =bvRX -----END PGP SIGNATURE-----