-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA512 # SSA-878278: Denial-of-Service Vulnerability in SIMATIC WinAC RTX (F) 2010 Publication Date: 2019-10-08 Last Update: 2020-01-14 Current Version: 1.1 CVSS v3.1 Base Score: 7.5 SUMMARY ======= A vulnerability in SIMATIC WinAC RTX (F) 2010 controller software could allow an attacker to perform a denial-of-service attack if a large HTTP request is sent to the network port of the host where WinAC RTX is running. Siemens has released SIMATIC WinAC RTX (F) 2010 incl. SP3 Update 1 that fixes the vulnerability, and recommends that customers update to this new version. AFFECTED PRODUCTS AND SOLUTION ============================== * SIMATIC WinAC RTX (F) 2010 - Affected versions: All versions < SP3 Update 1 - Remediation: Update to SIMATIC WinAC RTX (F) 2010 SP3 Update 1 - Download: https://support.industry.siemens.com/cs/ww/en/view/109772291 WORKAROUNDS AND MITIGATIONS =========================== Siemens has identified the following specific workarounds and mitigations that customers can apply to reduce the risk: * Restrict network access to the host containing the affected service. * If the service is not used as a server, configure Windows Firewall to disable communications on the port of the vulnerable service. GENERAL SECURITY RECOMMENDATIONS ================================ As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity PRODUCT DESCRIPTION =================== SIMATIC WinAC RTX (F) 2010 is a SIMATIC software controller for PC-based automation solutions. VULNERABILITY CLASSIFICATION ============================ The vulnerability classification has been performed by using the CVSS scoring system in version 3.1 (CVSS v3.1) (https://www.first.org/cvss/). The CVSS environmental score is specific to the customer's environment and will impact the overall CVSS score. The environmental score should therefore be individually defined by the customer to accomplish final scoring. An additional classification has been performed using the CWE classification, a community-developed list of common software security weaknesses. This serves as a common language and as a baseline for weakness identification, mitigation, and prevention efforts. A detailed list of CWE classes can be found at: https://cwe.mitre.org/. * Vulnerability CVE-2019-13921 Affected versions of the software contain a vulnerability that could allow an unauthenticated attacker to trigger a denial-of-service condition. The vulnerability can be triggered if a large HTTP request is sent to the executing service. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the service provided by the software. CVSS v3.1 Base Score: 7.5 CVSS Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:W/RC:C CWE: CWE-410: Insufficient Resource Pool ACKNOWLEDGMENTS =============== Siemens thanks the following parties for their efforts: * Tal Keren from Claroty for coordinated disclosure. ADDITIONAL INFORMATION ====================== For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories HISTORY DATA ============ V1.0 (2019-10-08): Publication Date V1.1 (2020-01-14): Added update for SIMATIC WinAC RTX (F) 2010 TERMS OF USE ============ Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use. -----BEGIN PGP SIGNATURE----- iQIcBAEBCgAGBQJeHQSAAAoJENP0geoRSq/kFm8QAIvDlQynaFsDlFeu+b3I3U11 flsLfCtVO/4bMzeNP7kQ5L0gs8Fc4ku9ySPrD2cI5uUglyx0Cf25JWbd7MeF28Vx YGdrE1bLXYIS+i3AEVXBuQNp1ObOzJFVU5VVIGuY+XasbcDovEeT+jm/yvARQq0H S81IAa9onzPKFvnzsyc1ay4Niq+jXivbVVqoF1CwsTPdZcxa5ZpzAmLP8I2P2fal eVRQ0uQ53s0kCjOcdiArg2kSLl1AGPelDyrVsiKi5KDnHzrPry1d90omS6L2BHUV ueMG7Eaweeuk7fvrVAeLowC1iJFjO3SX+ePJrZncC4X5SYa86ubhN30HmXQ7+hJW UKdaSqg2utL5G2rgLGfkouY9MIjc9DiuvefjMLp0Pgy9oSp3EPRIXYdWVztn0EI+ Hi2OJWmEDFrB0Q0e2IRUu5/OAqAn0KQfvfk+s/+pv0CnIq2oXU6qXzOApyIwPF6E MIwacjBg56W7NfoxPn+i6u865VLFANNfgsZ4FLact/ZlGlkPOU1zmFa8CeQ8gy4B VOKd3XBEQwiJr3sSJpCqAo4+zpWWPnvnDp9SEAkyiattu9s95RatRU/b4l88FChx SA6h/MbhQzIAco192gTYj6ST2sRdQFdr55cel5oto5Z0UySV3/blpMK7QnickU6b 4frLA4brdfhlnG7Aoxqx =tkVM -----END PGP SIGNATURE-----