-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA512 # SSA-931064: Authentication Bypass in SIMATIC Logon Publication Date: 2017-02-13 Last Update: 2018-06-12 Current Version: 1.4 CVSS v3.0 Base Score: 9.0 SUMMARY ======= The latest update for SIMATIC Logon fixes a security vulnerability that could allow attackers to circumvent user authentication under certain conditions. SIMATIC WinCC, SIMATIC PCS 7, SIMATIC PDM, and SIMATIC IT Production Suite provide SIMATIC Logon as component of the product. Installing the SIMATIC Logon update fixes the vulnerability for all products mentioned below. AFFECTED PRODUCTS AND SOLUTION ============================== * SIMATIC Logon - Affected versions: All versions < V1.5 SP3 Update 2 - Remediation: Update to V1.5 SP3 Update 2 - Download: https://support.industry.siemens.com/cs/ww/en/view/109744966 * SIMATIC WinCC - Affected versions: All versions < V7.4 SP1 - Remediation: Install SIMATIC Logon update (can be installed without WinCC update, see compatibility note on download page) - Download: https://support.industry.siemens.com/cs/ww/en/view/109744966 * SIMATIC WinCC Runtime Professional - Affected versions: All versions < V14 SP1 - Remediation: Install SIMATIC Logon update (can be installed without WinCC Runtime Professional update, see compatibility note on download page) - Download: https://support.industry.siemens.com/cs/ww/en/view/109744966 * SIMATIC PCS 7 - Affected versions: All versions < V8.2 SP1 - Remediation: Install SIMATIC Logon update (can be installed without PCS 7 update, see compatibility note on download page) - Download: https://support.industry.siemens.com/cs/ww/en/view/109744966 * SIMATIC PDM - Affected versions: All versions < V9.1 - Remediation: Install SIMATIC Logon update (can be installed without PDM update, see compatibility note on download page) - Download: https://support.industry.siemens.com/cs/ww/en/view/109744966 * SIMATIC IT Production Suite - Affected versions: All versions < V7.1 - Remediation: Install SIMATIC Logon update (can be installed without IT Production Suite update, see compatibility note on download page) - Download: https://support.industry.siemens.com/cs/ww/en/view/109744966 WORKAROUNDS AND MITIGATIONS =========================== Siemens has not identified any specific mitigations or workarounds. GENERAL SECURITY RECOMMENDATIONS ================================ As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals. Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity PRODUCT DESCRIPTION =================== SIMATIC Logon (SL) is a software application used for central user administration and access control in other SIMATIC applications. VULNERABILITY CLASSIFICATION ============================ The vulnerability classification has been performed by using the CVSS scoring system in version 3.0 (CVSS v3.0) (https://www.first.org/cvss/). The CVSS environmental score is specific to the customer's environment and will impact the overall CVSS score. The environmental score should therefore be individually defined by the customer to accomplish final scoring. * Vulnerability CVE-2017-2684 An attacker with knowledge of a valid user name, and physical or network access to the affected system could bypass the application-level authentication. CVSS v3.0 Base Score: 9.0 CVSS v3.0 Vector: CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:C/C:H/I:H/A:H/E:F/RL:O/RC:C ADDITIONAL INFORMATION ====================== For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories HISTORY DATA ============ V1.0 (2017-02-13): Publication Date V1.1 (2017-06-13): Added version information of WinCC 7.4 SP1, WinCC Professional V14 SP1 that include a fixed version of SIMATIC Logon V1.2 (2017-07-06): Added version information SIMATIC PCS 7 and SIMATIC PDM that include a fixed version of SIMATIC Logon V1.3 (2017-11-17): Added version information for SIMATIC IT Production Suite V1.4 (2018-06-12): New format, updated fixed PCS 7 version TERMS OF USE ============ Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use. -----BEGIN PGP SIGNATURE----- iQIcBAEBCgAGBQJbHw0AAAoJELtnleqOVdUuyfsQAJ3QDROVKfv2vzN6qMG2mv1m u6098wHXwGI2y61fXTreCdf0AsF0kTvtXJCgqEqHq3lU1jtemFq2UAKppEsJ1kBb lI8gBW8Yki9nfvS1/ggLPh8z6uoOTRw85ktFJwk1eLtEEHceVVxo7cfpgn0IXkQh DthIgWnyR3ZkpnSoc8GW7Uqh/coGiB5VnucvEp8VhnWhrzoijA+PIUfYSIdeGMQm O6PrKwJfJVI51mj2J1R6+DwJAW2SdwDQpupJXRknWn99ghinJIKWjXlecpcaFp0Q YTiAR2/eQZLoiPWWn+Og8IKE8559FCaIaGGfsrzWIaU+4APbuCSZ3EG/SJk7lRIl jLzSLc6E+5AyF5EGaGnMrhpcX3Ay33vV3O03EYQjHj8aZ4eNmAT+jdfbg7O77I4t CpksfC5QECw27UjsF5W9Axyfw8ymBq8k8foOHWK+3yJN7GGns08qZY7WghEXa2rF yBnNLgNH/sSGaQXSdaLhm/zvdqD0YOuGdzTEQlx73JZd+UQ7ihLy3q0eyvy3ooTO H9P2VGfQJtlRP4bKgcrYrCj3OfERUC6phQirNGp2GlALkHs8GEl5Mm75vp/IaIjw zTbt/iY0dhIUCbxGO7svzxI4sUIKgr7VzYk7xNCFx4Mrf3rs/KxZqfaGItIyS7pe U0EF9wkhXm6Ov+wUyaYz =RUhk -----END PGP SIGNATURE-----